Level Measurement Guide Sitrans F M Magflo
Process Instrumentation and Analytics
 
Level Measurement Guide
 

Reliable Level Measurement

It’s reliable. That’s what customers say about Siemens Miltonic’s technology installed in hundreds of thousands of industrial process applications worldwide. Siemens Miltonic’s is the global center for level measurement technology within Siemens Process Instrumentation. You can rely on our instruments for high performance: they provide cost-effective measurement of continuous level, point level, and interface in a wide range of applications, such as water and wastewater, chemical, petrochemical, pharmaceutical, mining, cement, aggregates, and bulk solids. This guide provides an overview of level measurement instruments to help you select the equipment and solution that best meet your needs.

Level measurement courses at the Siemens Miltonic’s Learning Center
Siemens Miltonic’s Process Instruments offers world-class level instrumentation training at our state-of-the-art learning center in Peterborough, Canada. For current information and schedules.

Million in one

Signal processing with field Experience
Siemens level measurement instruments come with extensive field experience. Siemens Miltonic’s developed the signal processing technology for level  instruments based on the experience of a million instruments in industrial applications. With this experience, we understand the importance of reliability, and we know what it takes to make a trusted and accurate level instrument for demanding applications. That’s why our engineers invented Sonic Intelligence® and Auto False-Echo Processing, and that’s why these instruments carry so many patents. With Siemens Miltonic’s you get the experience of a million applications in one instrument.

Sonic Intelligence
Our patented Sonic Intelligence signal processing  technology was developed using knowledge provided by our field service engineers from real application data. Siemens Miltonic’s’ instruments offer the unique advantage of this technology. Sonic Intelligence differentiates between true echoes from the material and  false echoes from obstructions or electrical noise. The sophisticated software is continuously updated and supported by field data gained from more than 500,000 ultrasonic and radar level applications. This in-depth knowledge and experience is built into the  software’s advanced algorithms to provide intelligent processing  of echo profiles. The result is repeatable, fast, and reliable measurement you can trust.

 


probe

SITRANS Probe
2-wire ultrasonic and radar level transmitters

SITRANS® Probe LU and SITRANS Probe
LRset the new standard for ultrasonic and radar continuous level measurement. These transmitters offer you  superior reliability for level, volume, and flow applications in the water and wastewater, food, chemical, and  hydrocarbon processing industries. SITRANS Probe is the award-winning Miltonic’s® The Probe taken to a higher level with innovative transducer and antenna designs, communications capability, and nineteen patents.

The result is greater accuracy and reliability for your continuous level measurement applications.

SITRANS Probe LU ultrasonic level measurement transmitter sets the standard for precision with an accuracy of 0.15%. The improved signal-to-noise ratio enhances Sonic Intelligence echo processing and Auto False-Echo Suppression to support the 0.15% accuracy and, as a result, guarantees reliability.



SITRANS Probe LR

2-wire, 5.8 GHz (6.3 in North America) radar transmitter for level/volume monitoring of liquids and slurries in storage and process vessels


probe

Range

20 m (65 ft)

Process temperature

-40 to 80 °C (-40 to 176 °F)

Process pressure

Up to 3 bar (43.5 psi g)

Key features

High signal-to-noise ratio,
comparable to a 4-wire device
■ Sonic Intelligence Echo Processing
■ Auto False-Echo Suppression
■ Level and volume measurement
■ 5.8 GHz (USA 6.3 GHz)
■ Infrared Intrinsically Safe (IS)
handheld programmer
■ Patented, shielded and hermetically
sealed polypropylene
antenna/process connection;
100 mm (4") shield standard
■ Rotating head aligns with conduit
for easy wiring

Options:
■ 250 mm (10") shield length

Output

■ 4 to 20 mA
■ Intrinsically safe

Communications

 

■ HART®
■ SIMATIC® PDM for remote
configuration and diagnostics

Power specifications

4 to 20 mA, 24 V DC nominal with
max. 550 Ohm, 30 V DC maximum

Approvals

CE, CSAUS/C, FM, ATEX, Lloyd’s Register
of Shipping, ABS, Industry Canada,
FCC, R&TTE


 



SITRANS Probe LU

2-wire, loop powered ultrasonic transmitter for level/volume/flow monitoring of liquids in storage vessels,  simple process vessels, and open channels.


probe


Range

6 m (20 ft) or 12 m (40 ft)

Process temperature

-40 to 85 °C (-40 to 185 °F)

Process pressure

0.5 bar (7.25 psi g)

Key features

High signal-to-noise ratio
■ Sonic Intelligence Echo Processing
■ Auto False-Echo Suppression
■ Level, volume and flow
measurement
■ Infrared Intrinsically Safe (IS)
handheld programmer
■ Built-in temperature compensation
■ Choice of threaded connections
■ ETFE or PVDF copolymer
transducer
■ Rotating head aligns with conduit
for easy wiring

Output

■ 4 to 20 mA
■ Intrinsically safe

Communications

HART or Profibus PA
■ SIMATIC PDM for remote configuration and diagnostics

Power specifications

HART: nominal 24 V DC with
max. 550 Ohm, 30 V DC
maximum, 4 to 20 mA
PROFIBUS: bus-powered, as per
IEC 61158-2; 12, 13, 15 or
20 m A depending on programming
(General Purpose or Intrinsically
Safe version)

Approvals

CE, CSAUS/C, FM, ATEX, Lloyd’s
Register of Shipping, ABS





 

 

 

 

 

 

 

 

 

 



   
   

Electro-mechanical point level switches
Electro-mechanical switches are rotating or vibrating point level switches for a cost-effective solution for  basic applications on powders, grains, and other dry solids.

SITRANS LPS200
Electro-mechanical rotary paddle switch for level detection of powder and granular solids with bulk densities as low as 35 g/ l (2.19 lb / ft3).


probe


Range

10 m (30 ft)

Process emperature

■ -20 to 80 °C (-4 to 176 °F)
■ -20 to 220 °C (-4 to 428 °F) HT model

Process pressure

Up to 0.5 bar (7.25 psi)
■ Up to 10 bar (145 psi) optional

Key Features

■ High or low level alarm
■ Densities as low as 100 g/l (6.25 lb/ft3) standard
■ Hinged paddle for densities as low as 35 g/l (2.19 lb/ft3).
■ Switch selectable power supply
■ Rota table enclosure
■ Unique friction clutch mechanism
■ Installation through process
connection 11⁄4" NPT or BSP
■ Compact, extended models and
cable extension up to 10 m (30 ft)
■ High temperature model
■ High pressure model

Output

Micro switch SPDT contact,
5A at 250 V AC, non-inductive

Communications

 

Power specifications

■ Jumper selectable
■ 115 V AC, ±15%, 50/60 Hz, 4 VA
230 V AC, ±15%, 50 Hz, 6 VA
24 V DC, ±15%, 2.5W

Approvals

CE, CSA, FM,
ATEX (dust ignition approvals)





 

 

 

 

 

 

 

 

   

 

SITRANS LVS200

Electro-mechanical vibratory switch for level detection of powder and granular solids with bulk densities as low as 20 g/ l (1.3 lb / ft3)

probe

Range

4 m (13 ft)

Process temperature

-40 to 150 °C (-13 to 302 °F)

Process pressure

Up to 10 bar (145 psi)

Key features

■ High or low level alarm
■ Compact design
■ Top, side, angle mount
■ Rotatable enclosure
■ Self-cleaning fork
■ Extended model up to 4
■ Interface model (solids in
■ Remote electronics option pipe extended model

Output

SPDT relay, 8A at 250 V AC,
non-inductive

Communications

 

Power specifications

19 to 230 V AC, +10%, 50/60 Hz,
8 VA
19 to 55 V DC, +10%, 1.5W

Approvals

CE, CSA, FM,
ATEX (dust ignition approvals)

 


Miltonic’s Tilt Switch

Electro-mechanical tilt switch for point level detection, plug chute detection, belt tracking and feed loss detection on conveyor belts

probe

Range

Switch changes state at
approximately 17° from vertical

Process temperature

Low temperature:
-40 to 90 °C (-40 to 194 °F)
■ High temperature:
-40 to 150 °C (-40 to 302 °F)

Process pressure

Not rated

Key features

■ High or low alarm
■ 304 stainless steel
■ Total encapsulated mercury switch
■ Easy installation and operation

Optional probe extensions:

■ Flat and cross paddles
■ Anti-wear
■ Float

Output

Single N.C. contact
5 Ohm max., 2A at 24 V DC

Communications

 

Power specifications

30 V DC (max.)

Approvals

CE




Frequency shift level switches

Pointek® CLS 100

Compact 2-wire inverse frequency shift capacitance switch for level detection in constricted spaces, interfaces, solids, liquids, slurries, and foam.

probe

Range

100 mm (4")

Process temperature

-40 to 100 °C (-40 to 212 °F)

Process pressure

Up to 10 bar (145 psi)

Key features

Inverse frequency technology
■ Sensitivity adjustment

Options:

■ Intrinsically Safe
■ Dust-ignition proof
■ Non-hazardous general purpose
■ Sense Guard for abrasive
applications
■ PPS or PVDF probes
■ IP68

Output

4 to 20/20 to 4 mA 2-wire
current loop
■ Solid-state or relay switch
■ Relay output (all synthetic
version)

Communications

 

Power specifications

Standard: 10 to 33 V DC
■ Intrinsically Safe: 10 to 30 V DC

Approvals

CE, CSA, FM, ATEX
Lloyd’s Register of Shipping,
ABS, WHG

 


Pointek CLS 200
Inverse frequency shift capacitance switch with a high level of chemical resistance; ideal for level detection of interfaces, solids, liquids, slurries, and foam, and for simple pump control.

probe

Range

Rod: 5.5 m (18 ft)
Cable: up to 35 m (115 ft)

Process temperature

-40 to 125 °C (-40 to 257 °F)

Process pressure

Up to 25 bar (365 psi)
■ Up to 10 bar (145 psi)
cable version

Key features

Inverse frequency technology
■ Level detection independent of
tank wall/pipe
■ High/low gain switch
■ Suitable for hazardous areas
■ Multiple outputs
■ Fully adjustable hysteresis

Options:

■ Rigid, cable and sanitary
■ SensGuard for abrasive
applications
■ Thermal isolator
■ Non-hazardous general purpose

Output

Analog model:
■ 1 form C (SPDT) relay
■ Solid-state switch
Digital model:
■ Solid-state switch
■ Relay or mA output

Communications

■ Digital model: PROFIBUS PA
■ Analog model: 3 LED indicators

Power specifications

12 to 250 V AC/DC, 50/60 Hz,
2VA/2W max.

Approvals

CE, CSA, FM, ATEX, 3A
Lloyd’s Register of Shipping,
ABS, WHG

 


Pointek CLS 300
Inverse frequency shift capacitance level switch for detecting interfaces, solids, liquids, slurries and viscous materials in demanding conditions of low/high pressure, high temperatures, and corrosive and abrasive materials.

probe

Range

Rod: 1 m (40") Cable: 25 m (82 ft)

Process temperature

-40 to 200 °C (-40 to 392 °F)
■ -40 to 400 °C (-40 to 752 °F)
HT version

Process pressure

Up to 35 bar (508 psi)

Key features

Patented Active-Shield technology
■ Universal transmitter
■ Multiple outputs
■ 5 dipswitches for special
adjustments e.g. fail safe,
high/low

Options:

■ Extensions up to 25 m (82 ft)
■ Thermal isolator
■ High temperature (HT version)

Output

Analog model:
■ 1 form C (SPDT) relay
■ Solid-state switch
Digital model:
■ Solid-state switch
■ Relay or mA output

Communications

Digital model: PROFIBUS PA
■ Analog model: 3 LED indicators

Power specifications

12 to 250 V AC/DC, 50/60 Hz,
2VA/2W max.

Approvals

CE, CSA, FM, ATEX
Lloyd’s Register of Shipping,
ABS, WHG



 


Pointek CLS 500

Inverse frequency shift capacitance point level switch for detecting interfaces, solids, liquids, slurries and viscous materials in critical conditions of extreme temperature and extreme pressure.

probe

Range

Rod: 1 m (40") Cable: 25 m (82 ft)

Process temperature

-40 to 200 °C (-40 to 392 °F)
■ -40 to 400 °C (-40 to 752 °F)
HT version

Process pressure

Up to 35 bar (508 psi)

Key features

Patented Active-Shield technology
■ Universal transmitter
■ Multiple outputs
■ 5 dipswitches for special
adjustments e.g. fail safe,
high/low
Options:
■ Extensions up to 25 m (82 ft)
■ Thermal isolator
■ High temperature (HT version)

Output

Analog model:
■ 1 form C (SPDT) relay
■ Solid-state switch
Digital model:
■ Solid-state switch
■ Relay or mA output

Communications

Digital model: PROFIBUS PA
■ Analog model: 3 LED indicators

Power specifications

12 to 250 V AC/DC, 50/60 Hz,
2VA/2W max.

Approvals

CE, CSA, FM, ATEX
Lloyd’s Register of Shipping,
ABS, WHG

 


Frequency shift level measurement

SITRANS LC 300

Inverse frequency shift capacitance level transmitter for liquids and solids, high accuracy applications such as food and beverages, pet food and bulk solids; ideal for challenging processes involving vapor and dust.

probe

Range

Rod: 5.0 m (16.4 ft) Cable: 25 m (82 ft)

Process temperature

-40 to 200 °C (-40 to 392 °F)

Process pressure

Up to 35 bar (511 psi)

Key features

Push-button calibration
■ Patented Active-Shield
technology
■ Integrated local display

Output

4 to 20/20 to 4 mA
2-wire current loop

Communications

9-32 V DC any polarity, 2-wire
current loop circuit (9 V at 22 mA)

Power specifications

 

Approvals

CE, CSANRTL/C, FM, ATEX
Lloyd’s Register of Shipping, ABS,
Bureau Veritas, current signaling
according to NAMUR NE 43




SITRANS LC 500
Inverse frequency shift capacitance level and interface transmitter for extreme and critical process conditions, such as oil and liquid gas, toxic and aggressive chemicals and vapors.

probe

Range

Rod: 5.5 m (18 ft) Cable: 35 m (115 ft)

Process temperature

-40 to 200 °C (-40 to 392 °F) optional: up to 400 °C (752 °F) down to -200 °C (-328 °F)

Process pressure

Up to 200 bar (2920 psi)
Option: Up to 525 bar (7665 psi)

Key features

■ Pre-detection alarm
■ Pump control
■ Patented Active-Shield technology
■ Push-button calibration
■ One-point calibration
■ Integrated local display
■ Full-function diagnostics
Options:
■ High temperature
■ High pressure
■ Sanitary
■ Customized application design
■ Process connections and
sensor options
■ Custom materials

Output

■ 4 to 20/20 to 4 mA
2-wire current loop
■ Solid-state switch

Communications

HART

Power specifications

■ 12 to 33 V DC, (30 V DC for IS) at
3.6 mA, 9.5 to 33 V DC,
(30 V DC for IS) at 22 mA
■ 3.6 to 22 mA/22 to 3.6 mA
(2-wire current loop)

Approvals

CE, CSANRTL/C, FM, ATEX
Lloyd’s Register of Shipping, ABS,
3A, Bureau Verities, current signaling
according to NAMUR NE 43




SITRANS PD 500
Inverse frequency shift capacitance 2-wire switch for interface and product presence detection, even in extreme and critical process conditions; suitable for use on any ferrous or non-ferrous piping system.


probe

Range

Fitting length: 55 mm (2.1")

Process temperature

-40 to 200 °C (-40 to 392 °F)
optional: up to 400 °C (752 °F)
down to -200 °C (-328 °F)

Process pressure

Up to 50 bar (725 psi)
Option:Up to 200 bar (2920 psi)

Key features

■ Flange and sandwich mounting,
according to ANSI and DIN
standards
■ Integrated local display
■ Full-function diagnostics
■ Stainless steel AISI 316L process
connection
Options:
Process connections:
Carbon steel C35

Output

■ 4 to 20/20 to 4 mA
2-wire current loop
■ Solid-state switch

Communications

■ HART
■ SIMATIC PDM compatible

Power specifications

■ 12 to 33 V DC, (30 V DC for IS)
at 3.6 mA, 9.5 to 33 V DC,
(30 V DC for IS) at 22 mA
■ 3.6 to 22 mA/22 to 3.6 mA
(2-wire current loop)

Approvals

CE, FM/CSA, FM, ATEX
Lloyd’s Register of Shipping
current signaling according to
NAMUR NE 43








Radar level measurement

SITRANS LR 200

2-wire loop-powered pulse radar level transmitter for liquid bulk storage or simple process vessels

probe

Range

20 m (66 ft)

Process
temperature

-40 to 200 °C (-40 to 392 °F)

Process
pressure

Up to 40 bar (580 psi) process
connection type dependent

Key features

■ Level, space, distance and
volume measurement
■ Infrared Intrinsically Safe
handheld programmer
■ Auto False-Echo Suppression and
Sonic Intelligence
■ 5.8 GHz (USA 6.3 GHz)
■ Patented, shielded and
hermetically sealed polypropylene
antenna/process connection;
100 mm (4") shield standard
Options:
■ 250 mm (10") shield length
■ Process connections and antenna
options (see page 9)

Output

4 to 20 mA 2-wire current loop

Communications

■ HART or PROFIBUS PA
■ SIMATIC PDM for configuration
and diagnostics

Power
specifications

4 to 20 mA loop, 24 V DC nominal,
30 V DC max.
Minimum voltage depends on total
loop resistance

Approvals

CE, CSANRTL/C, FM, ATEX, ANZEx,
IECEx, PED, Lloyd’s Register of
Shipping, ABS Type Approval, 3A,
Industry Canada, FCC, R&TTE

 

   
   

SITRANS LR 300
Pulse radar level instrument for liquids and slurries in process vessels and extreme or hazardous process conditions.

probe

Range

20 m (66 ft)

Process
temperature

-40 to 200 °C (-40 to 392 °F)

Process
pressure

Up to 40 bar (580 psi) process
connection type dependent

Key features

■ Level, space, distance and
volume measurement
■ Infrared Intrinsically Safe
handheld programmer
■ Auto False-Echo Suppression
■ 5.8 GHz (USA 6.3 GHz)

Options:

■ Stainless steel enclosure
■ Sanitary
■ Purging (self-cleaning)
■ Process connections and antenna
options (see page 9)

Output

4 to 20 mA

Communications

■ Modbus® ASCII/RTU
■ HART
■ SIMATIC PDM for configuration
and diagnostics
Option:
PROFIBUS PA

Power
specifications

■ Universal AC/DC
■ 48 to 230 V AC, ±15%,
40 to 70 Hz, 28 VA/11W
■ 24 to 230 V DC, ±15%, 9W

Approvals

CE, CSANRTL/C, FM, ATEX,
Lloyd’s Register of Shipping,
ABS Type Approval, 3A,
Industry Canada, FCC, R&TTE

   
   

SITRANS LR 400
4-wire FMCW radar level transmitter for high power and long range measurement of solids and liquids; ideal  for extreme dust or low dielectric liquids.

probe

Range

50 m (164 ft)

Process temperature

-40 to 200 °C (-40 to 392 °F)
optional: up to 250 °C (482 °F)

Process pressure

Up to 40 bar (580 psi) process
connection type dependent

Key features

■ Level and volume
measurement
■ Infrared Intrinsically Safe
handheld programmer
■ Auto False-Echo Suppression
■ Self-calibration with internal
reference
■ 24 GHz FMCW and high signalto-
noise ratio

Options:

■ High temperature extension
■ Purging (self-cleaning)
(liquids version)

Output

■ 4 to 20 mA
■ 1 Relay

Communications

■ HART or PROFIBUS PA
■ SIMATIC PDM for configuration
and diagnostics

Power specifications

■ 120 to 230 V AC, ±15%, 50/60 Hz,12 VA/6W
■ 24 V DC, +25/-20%, 6W (optional)

Approvals

CE, CSANRTL/C, FM, ATEX,
Lloyd’s Register of Shipping,
ABS Type Approval, Industry Canada,
FCC, R&TTE, CETECOM




 

 

 

 

 

 

 

 

 

 

   
   

Ultrasonic level measurement

Multi Ranger® 100/200

Versatile short- to medium-range ultrasonic single- and multi-vessel level monitor / controller for virtually any application in a wide variety of industries.

probe

Range

5 m (50 ft) transducer and
material dependent

Process temperature

Transducer dependent

Process pressure

Transducer dependent

Key features

100 version:
■ Simple pump control
200 version:
■ Enhanced pump control
■ Differential control
■ Open Channel Flow monitor
■ Volume conversion
■ One mA input
Both versions:
■ Single or dual point
■ AC or DC
■ Digital input for back-up level
override from a point level
device (e.g. Pointek CLS 200)
■ Two discrete inputs
■ Wall or panel mount

Output

■ 3 relays standard
■ 6 relays (option)
■ Two 4 to 20 mA outputs (isolated)

Communications

■ Built-in Modbus RTU or ASCII
via RS-485
■ Compatible with SIMATIC PDM
via Modbus RTU
Options:
■ Dolphin Plus
■ Smart Linux® (see page 14)
- PROFIBUS DP
- Allen-Bradley® RIO
- Device Net™

Power specifications

■ AC version: 100 to 230 V AC
±15%, 50/60 Hz, 36 VA/17W
■ DC version: 12 to 30 V DC 20W

Approvals

CE, CSANRTL/C, UL Listed, FM
Lloyd's Register of Shipping, ABS




   
  .

 


SITRANS LU
Ultrasonic long-range level monitoring system for liquids and solids.
LU 01: 1 point
LU 02: 2 points
LU10: up to 10 points

probe

Range

60 m (200 ft) transducer and
material dependent

Process temperature

Transducer dependent

Process pressure

Transducer dependent

Key features

■ High/low alarm
■ Multi-point measuring:
2 (LU 02)
10 (LU 10)
■ Differential or average
measurement
■ Volume conversion
■ Priority scanning (LU 10)
■ Programmable with handheld
programmer or PC

Options (LU 10):

■ LU AO Analog Output Module
■ LU SAM Satellite Alarm Module

Output

■ 4 relays (LU 01, LU 02)
■ Up to 40 relays (LU 10)
■ 4 to 20 mA (isolated)

Communications

■ Dolphin RS-232/RS-485
(LU 01, LU 02)
■ Dolphin via infrared (LU 10)
Option:
Smart Linux (see page 14)
- PROFIBUS DP
- Allen-Bradley RIO
- Device Net

Power specifications

■ LU 01, LU 02 – AC version:
100/115/200/230 V AC or
DC version: 18 to 30 V DC, 25 W
■ LU10: 100/115/200/230 V AC

Approvals

CE, CSANRTL/C, FM
Lloyd’s Register of Shipping, ABS

   
   

Hydro Ranger 200
Ultrasonic level controller for  up to 6 pumps – control, differential control, and open channel flow monitoring.

probe

Range

15 m (50 ft) transducer and
material dependent

Process temperature

Transducer dependent

Process pressure

Transducer dependent

Key features

■ Single or dual point
■ Fixed and rotating pump
rosters
■ Ratio pump runtimes
■ Controls up to 6 pumps
■ Screen rake automation
■ Influent and effluent monitor
■ Open Channel Flow monitor
■ Remote collection monitor
■ Sampler control
■ Volume conversion
■ Scum line reduction
■ High level back-up alarm input
■ One mA input
■ 2 discrete inputs
■ AC or DC
■ Wall or panel mount

Output

■ 6 relays standard
■ Two 4 to 20 mA outputs
(isolated)

Communications

■ Built-in Modbus RTU/ASCII via
RS-485
■ Compatible with SIMATIC PDM
via Modbus RTU
Options:
■ Dolphin Plus
■ Smart Linux
- PROFIBUS DP
- Allen-Bradley RIO
- Device Net

Power specifications

■ AC version: 100 to 230 V AC
±15%, 50/60 Hz, 36VA/17W
■ DC version:12 to 30 V DC 20W

Approvals

CE, CSANRTL/C, UL Listed, FM, Lloyd's
Register of Shipping, ABS, MCERTS

   
   


SITRANS LUC 500
Complete ultrasonic level controller for monitoring and control of water distribution and wastewater collection systems, with energy-saving algorithms.

probe

Range

15 m (50 ft) transducer and
material dependent

Process temperature

Transducer dependent

Process pressure

Transducer dependent

Key features

■ Fixed and rotating pump rosters
■ Ratio pump runtimes
■ Time based control options
■ Screen rake automation
■ Influent and effluent monitor
■ Remote collection monitor
■ Sampler control
■ Open channel flow monitor
■ RTU and data logger
■ Volume conversion
■ Discrete inputs for pump
interlocks/pump faults feedback
■ Report by exception
■ Combined Sewer Overflow
(CSO) logging
Options:
■ VS 100 Velocity Sensor
■ Wall, rack or panel mount

Output

5 relays, 4 to 20 mA (option)

Communications

Telemetry capability with Modbus
RTU/ASCII via RS-232/RS-485
Options:
■ Dolphin Plus
■ Smart Linux
- PROFIBUS DP
- Allen-Bradley RIO
- Device Net

Power specifications

■ AC version:100 to 230 V AC ±15%,
50/60 Hz, 36VA/17W
■ DC version: 12 to 30 V DC 20W

Approvals

CE, CSANRTL/C, UL Listed


 